Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Ref 2.27.1.15 Telephone non functional with narmal power off. Battery back up needs replaced 1/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x Ref 2.27.3.1.6(h) No Audible signal om Phase I Recall operation. However the Visual did work, must Re-inspect when violation corrected. Must correct by 7/9/20. 1/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door needs to be self-locking 10/19/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 The current year MCP has not been posted in the Elevator Machine Room. Fire Service Test Log is good & 2021 MCP is in the machine room.