ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
Ref 2.27.3.1.6(h) No Audible signal om Phase I Recall operation. However the Visual did work, must Re-inspect when violation corrected. Must correct by 7/9/20.
|
1/13/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room door needs to be self-locking
|
10/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
The current year MCP has not been posted in the Elevator Machine Room. Fire Service Test Log is good & 2021 MCP is in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Ref 2.27.1.15 Telephone non functional with narmal power off. Battery back up needs replaced
|
1/13/2021
|