ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
5/27/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
|
|
Post In Case of Fire Do Not Use Elevator signage next to hall button fixture at each landing.
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
|
|
Need to replace plunger seal. Seal leaks excessively during annual pressure relief test.
|
6/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove standing oil and water from elevator pit.
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
|
|
Remove scavenger pump from pit. Cylinder drain lines can not drain into scavenger pump.
|
12/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
|
|
Remove scavenger pump from pit. Cylinder drain lines need to drain into covered pit collection container of no more than 5 gallon capacity.
|
5/27/2021
|