ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post the current state operating certificate.
|
11/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.6 - Governor-rope tension devices
|
8.11.2.1.5(g)
|
|
|
Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Provide proper hoistway door safety retainers to confrom to A17.2 - 4.2.1(c)
|
3/28/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
|
The installation of the smoke detectors, heat detectors, and shunt trip shall be completed and tested.
|
6/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal all voids and penetrations in the hoistway and properly secure the ceiling of the hoistway.
|
6/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
Receptacle for sump pump shall be located at a minimum 48" or greater above the pit floor.
|
6/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
Complete installation of battery back up system and test back up system.
|
6/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
The finished floor at each landing shall be level with the hoistway entrance sill.
|
6/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency telephone shall work.
|
7/5/2018
|