ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
|
|
There is not a manual shutoff valve accessible to elevator personnel outside of the hoistway.
|
8/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.37 - Pressure Switch
|
3.26.8 Pressure Switch
|
|
|
There is not a pressure switch installed as per 2004 code requirements
|
8/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.31 - Relief Valves
|
8.11.3.1.2(n)
|
|
|
There is not a connection on valve for attachment of gauge outside of the hositway to read relief pressure during pressure test.
|
8/12/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
8.11.3.1.2 (o)
|
|
|
There is not a manual lowering valve accessible to elevator personnel outside the hoistway as required per code.
|
6/18/2020
|