ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
3.4
|
x
|
|
3.4.1.3 - The hoistway pit refuge space shall be clearly and permanently marked "REFUGE SPACE."
|
8/17/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
6/17/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
Installation placed in Inactive Status. Locked out & Red Tagged. Inactive status allowed for a maximum of 2 years.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.4
|
|
|
Manual lowering shall be accessible from outside the hoistway. - Customer shall apply for a variance.
|
2/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19.4.1
|
|
|
Oil line shutoff shall be accessible from outside the hoistway. - Customer shall apply for a variance.
|
2/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
|
|
Pressure gauge fitting shall be accessible from outside the hoistway. - Customer shall apply for a variance.
|
2/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
6/17/2022
|