ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Fire gibs are missing from hoistway doors.
|
1/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
4/16/2024
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
|
|
2.20.9.8.2 - Suspension rope tail ends shall be properly seized/banded. Electrical tape is not proper.
|
4/16/2024
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
|
|
2.20.9.4 - Hoist rope tail retaining clips shall be properly spaced.
|
4/16/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/16/2024
|