Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Replace the emergency light battery 1/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Hydraulic muffler inside hydraulic tank has excessive leak when performing pressure test. Repair/replace 1/4/2019
MO Minimum : Elevators (I) - Pits (I)1 clean up the pit 1/11/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Clean up the oil spill in the pit. 3/22/2023
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) x Replace the leaking packing gland as it is leaking excessively 2/14/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as there is no dial tone 2/14/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Need current operating certificate 1/4/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(d) Provid a written Maintenance Control Program in the machine room 12/23/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean down the hoistway top to bottom 12/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Repack the leaking jack and clean up the pit 1/11/2022