A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.2.1.5(a)
|
|
|
Channel pit floor to sump pump in drain standing water. 2.2.2.3
|
1/5/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
Channel Pit Floor to sump pump to drain Standing water in pit 2.2.2.3
|
1/5/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Complete annual CAT 1 test
|
11/12/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
2/19/2019
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Hoisting belts have red rouge all over needs to be replaced
|
10/19/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Need maintenance control program on site posted on controller on or by next test
|
12/21/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Need testing procedures in the MCP on or before 1/1/22
|
12/20/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit shall be kept clean and dry.
|
3/25/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
reinspectin for rouge on hoisting belts, no engineer letter supplied to me, 15 days to either receive letter from engineer stating belts are ok or the belts to be replaced or a rd tag unit place out of service.
|
1/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Remove water from pit
|
11/1/2019
|
A17.1-2016 : Elevators
|
3.6 - Final and emergency terminal stopping devices
|
8.11.2.1.3(h)
|
x
|
x
|
Repair bottom final limits switch operations 2.25.3.2
|
11/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
2.17.15
|
x
|
|
Repair governor tail sheave switch
|
11/12/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Repair machine space hoistway-top lighting
|
|
A17.1-2016 : Elevators
|
5.6 - Governor-rope tension devices
|
8.11.2.1.5(g)
|
|
|
Replace rusting conduit to governor tail sheave switch 620.21
|
1/5/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
x
|
|
Shorten Governor rope 2.18.6.4
|
11/21/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
x
|
|
Tested fire service failed
|
|