Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage x Repair switch push buttons in phase 2 fire service panel in car
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 2/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Remove Water from pit 11/1/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Need maintenance control program on site posted on controller on or by next test 12/21/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Need testing procedures in the MCP on or before 1/1/22 12/20/2021
A17.1-2016 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) Replace rusting conduit to Governor tail sheave switch 620.21 1/3/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) Channel pit floor to sump pump to drain standing water. 2.2.2.3 1/3/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(f) Repair machine space lighting top of hoistway 2.7.6.3.2(c) 1/3/2023
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Hoisting belts have rouge all over need to be replaced 10/19/2023
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Replace rusting pipe to govenor weight tail switch 10/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Replace rusting piping to governor weight tasil switch has not been corrected 11/3/2023
MO Minimum : Elevators (I) - Pits (I)1 x Reinspection for rusted piping for tail shiv in pit, not corrected. Will have until Jan 15, 2024 to complete 1/15/2024