Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
Yes
|
No
|
Emergency stop switch and alarm shall work on normal and 4hr battery back up power. Does not work on either.
|
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
Yes
|
No
|
The safety pan under platform shall stop the car and needs to be repaired.
|
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1
|
No
|
No
|
Requires signage stating "in case of fire, use stairs".
|
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1 (Re-Inspect)
|
Yes
|
No
|
Under platform safety pan shall be operational.
|
4/17/2025
|
|
Missouri Minimum : Platform Lifts
|
(U) - Existing Vertical and Inclined Platform Lifts
|
(U)1
|
No
|
No
|
The disconnect shall be lockable.
|
6/27/2025
|