Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) Yes No Emergency stop switch and alarm shall work on normal and 4hr battery back up power. Does not work on either.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No Requires signage stating "in case of fire, use stairs".
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 No No The disconnect shall be lockable. 6/27/2025
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) Yes No The safety pan under platform shall stop the car and needs to be repaired.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) Yes No Under platform safety pan shall be operational. 4/17/2025