A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
8.11.3.1.1(d)
|
|
|
new cab floor covering is not as thick as the old covering, there is now a trip hazard because of the height difference between the cab floor and the car sill
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.1.1 Not less than two lamps
|
|
|
Replace burnt out lightbulb in elevator cab ceiling fixture
|
11/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Perform monthly fire service test and post log in the Machine Room.
|
2/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.8.4
|
|
|
machine room was hot, the air conditioning unit does not appear to be working correctly, room shall be maintained to the temperature and humidity indicated on the elevator controller door
|
1/5/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection)
|
x
|
|
fire service phase 2 light on the car operating panel did not come on
|
1/23/2024
|