Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x fire service phase 2 light on the car operating panel did not come on 1/23/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.8.4 machine room was hot, the air conditioning unit does not appear to be working correctly, room shall be maintained to the temperature and humidity indicated on the elevator controller door 1/5/2023
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.11.3.1.1(d) new cab floor covering is not as thick as the old covering, there is now a trip hazard because of the height difference between the cab floor and the car sill 12/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Perform monthly fire service test and post log in the Machine Room. 2/11/2020