ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone not owrking
|
1/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection)
|
x
|
|
the fire service audible signal in the elevator did not work, repair audible signal
|
1/23/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Repair hole in machine room ceiling Sheetrock
|
11/11/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Speaker not working
|
1/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
x
|
|
In Case of Fire signage
|
1/10/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
Machine room air conditioner is dripping water onto the machine room floor, clean the drain line (2.8.5.3)
|
11/11/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
Machine room air conditioner not working, repair air conditioner to maintain machine room to the temperature and humidity level per the data tag on the elevator equipment (2.7.9.2)
|
11/11/2024
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.11.3.1.1(r)
|
x
|
|
repair the door restrictor, it is not working
|
11/30/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
x
|
|
penetrations need to be filled and pit cleaned
|
1/10/2019
|