Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Yes No Replace any missing fire tabs on hoistway doors. 12/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Fire service testing must be documented monthly. 12/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Replace faded/unreadable Phase 1 switch bezel. 12/2/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 8.11.2.1.4(l) Yes No Testing of emergency power shall be conducted on the car with weights. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) Yes Yes All phases of fire service and and initiating devices shall be tested. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Yes No Provide lobby warning placards on 2nd and 3rd floors. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) Yes No Provide testing of emergency brake. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Emergency power shall be tested. 2/19/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Emergency power operation of the elevator was tested, but did not work properly. Emergency power operation of the elevator shall be operational and shall be tested for compliance. 11/18/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) Yes No Provide a finished floor in the elevator car. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) Yes No Door closing force shall be tested and recorded. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work with 24/7 support. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate. 3/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate. 3/27/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Yes No The pit shall be cleaned. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Yes No The sump pump shall be tested and a sump pump cover shall be installed. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Yes No 2.11.10.2/IBC - Provide permanent lobby lighting on all floors. 8/23/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.1 Not less than two lamps Yes No 2.11/NEC - Provide feeder locations (Main and 110V) on controller disconnect. 8/23/2018