Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(b) No No Maintenance Control Program in place does not comply with code. 5/7/2026
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No Overspeed valve is sealed but not tagged. 5/7/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Observed no elevator certificate framed in machine room. 5/7/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevator is equipped with emergency power which shall be tested annually.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes All emergency fire service features shall be tested including heat detectors, smoke detectors, shunt trip disconnect, phase 1 & 2 emergency operation, and stand-by power operation. 6/27/2018