Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Main line disconnecting switch missing code mandated safety decals. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19 Anchor run of supply piping. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.11.10 Anchor hoistway sheet metal between floors. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.7 - Car leveling and anticreep devices 8.11.2.1.3(j) x Repair anti-creep leveling. 5/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.31 - Relief Valves 8.11.3.1.2(n) Seal control valve relief setting in machine room. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 2.11.11.1 Hang landing sill guards flush. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 8.11.2.1.2(a) The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating certificate shall be obtained and displayed. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.7.1.8 Install a code data plate. It shall read: A17.1-2004. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit of dirt and debris. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Remove all non-elevator related materials from the machine room. Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Install hoistway door fire tabs. 10/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The machine room door shall be self-locking, self-closing, and operable from the interior space without the use of a key. 12/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 2.25.2 x Bottom directional limit inoperative, repair. 5/18/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.4 - Normal terminal stopping devices 2.25 x The bottom directional limit shall activate before the car hits the buffer. Take corrective action as needed. 11/28/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency phone does not work. Initiate the necessary corrective action. 11/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In cab emergency telephone shall work. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x A permanent floor in the cab shall be installed. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x Sump drain needs anchoring. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) x Need sign on elevator elevator machine room door indicating elevator equipment. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) x Install a ceiling in the hoistway and seal all penetrations and voids in the hoistway. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits x Complete sump pump system and oil minder. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x Missing sprinkler head in the pit. 7/24/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Car emergency telephone shall work. 7/27/2018