ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
2.11
|
|
|
Install hoistway door fire tabs.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.11.10
|
|
|
Anchor hoistway sheet metal between floors.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
|
|
Hang landing sill guards flush.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Complete sump pump system and oil minder.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.4 - Normal terminal stopping devices
|
2.25
|
x
|
|
The bottom directional limit shall activate before the car hits the buffer. Take corrective action as needed.
|
11/28/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.5 - Normal terminal stopping device
|
2.25.2
|
x
|
|
Bottom directional limit inoperative, repair.
|
5/18/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
Main line disconnecting switch missing code mandated safety decals.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
The machine room door shall be self-locking, self-closing, and operable from the interior space without the use of a key.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
|
|
Anchor run of supply piping.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current state operating certificate shall be obtained and displayed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
8.11.2.1.1(d)
|
x
|
|
A permanent floor in the cab shall be installed.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In cab emergency telephone shall work.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Car emergency telephone shall work.
|
7/27/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency phone does not work. Initiate the necessary corrective action.
|
11/28/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
8.11.2.1.2(d)
|
x
|
|
Need sign on elevator elevator machine room door indicating elevator equipment.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
Sump drain needs anchoring.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
Missing sprinkler head in the pit.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(k)
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.7 - Car leveling and anticreep devices
|
8.11.2.1.3(j)
|
|
x
|
Repair anti-creep leveling.
|
5/18/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
x
|
|
Install a ceiling in the hoistway and seal all penetrations and voids in the hoistway.
|
7/24/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.31 - Relief Valves
|
8.11.3.1.2(n)
|
|
|
Seal control valve relief setting in machine room.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean the pit of dirt and debris.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Remove all non-elevator related materials from the machine room. Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.7.1.8
|
|
|
Install a code data plate. It shall read: A17.1-2004.
|
|