                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.15 - sign and operating device symbols
                     | 
                    
                        8.11.2.1.1(o)
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide Emergency Signs ("In Case of Fire...") at all landings adjacent to all hall call fixtures
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.15 - sign and operating device symbols
                     | 
                    
                        8.11.2.1.1(o)
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide a 3-inch international symbol for emergency medical services (Star of life) on both sides of the hoistway door frame
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.5 - Car lighting and receptacles
                     | 
                    
                        8.11.2.1.1(e) Car Lighting
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide working standby (emergency) lighting inside the car when the normal power fails
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Test the two-way communication means inside the car (program)
                     | 
                    
                        4/25/2018
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.10 - Numbering of elevators, machines, and disconnect switches
                     | 
                    
                        8.11.2.1.2(j)
                     | 
                    
                     | 
                    
                     | 
                    
                        :All disconnecting means in the machine room shall be provided with signs to identify the location of the supply side overcurrent protective devices
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.3 - Lighting and receptacles
                     | 
                    
                        8.11.2.1.2(c)
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide a disconnecting means that is an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position for the 110V car lights installed
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.41 - Maintenance Records
                     | 
                    
                        8.6.1.4
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide a written test procedure for obtaining the mechanical tripping speed for the governor per the Maintenance Control Program
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        3.10 - Hoistway construction
                     | 
                    
                        8.11.2.1.3(p)
                     | 
                    
                     | 
                    
                     | 
                    
                        Enclose/Seal all  seams/holes/penetrations in the hositway with fire-resistive construction/material
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        2.2.2 Design and Construction of Pits
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide a clearance of not less than 0.8 inches (20 mm) for the pit ladder and the side of the car
                     | 
                    
                        8/30/2019
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        6.4 - Firefighters' service (A17.1b-1989 and later editions)
                     | 
                    
                        2.27.2-2.27.8
                     | 
                    
                            x
                     | 
                    
                            x
                     | 
                    
                        :Need to test/inspect FireFighters' Emergency Operation (FEO) RECALL, smokes, heats, shunts, hoistway venting, alarm panel,
                     | 
                    
                        4/25/2018
                     |