Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Provide Emergency Signs ("In Case of Fire...") at all landings adjacent to all hall call fixtures 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Provide a 3-inch international symbol for emergency medical services (Star of life) on both sides of the hoistway door frame 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting Provide working standby (emergency) lighting inside the car when the normal power fails 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Test the two-way communication means inside the car (program) 4/25/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) :All disconnecting means in the machine room shall be provided with signs to identify the location of the supply side overcurrent protective devices 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Provide a disconnecting means that is an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position for the 110V car lights installed 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a written test procedure for obtaining the mechanical tripping speed for the governor per the Maintenance Control Program 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) Enclose/Seal all seams/holes/penetrations in the hositway with fire-resistive construction/material 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Provide a clearance of not less than 0.8 inches (20 mm) for the pit ladder and the side of the car 8/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x :Need to test/inspect FireFighters' Emergency Operation (FEO) RECALL, smokes, heats, shunts, hoistway venting, alarm panel, 4/25/2018