MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work, needs repaired. Re-inspection required
|
7/3/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency alarm in car does not work, needs repaired. Re-inspection required
|
2/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required
|
7/3/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
x
|
|
Platform guards at front and rear of car have vertical faces that are 44" in lieu of the minimum of 48". A variance has been applied for to allow due to short pit. New elevator installed in existing hoistway with structural impediments to excavation of the pit.
|
1/6/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
2/13/2024
|