Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 2/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency alarm in car does not work, needs repaired. Re-inspection required 2/13/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work, needs repaired. Re-inspection required 7/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 7/3/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 2.15.9 x Platform guards at front and rear of car have vertical faces that are 44" in lieu of the minimum of 48". A variance has been applied for to allow due to short pit. New elevator installed in existing hoistway with structural impediments to excavation of the pit. 1/6/2020