Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 2/13/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevator would not run on emergency power. Re-inspection required 2/14/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 7/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car is not working, needs repaired. Re-inspection required 6/16/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Previous violations that still need to be corrected: Test drive machine brakes with 125% of rated load. Test car safeties with rated load at rated speed. Test car buffer at rated speed with rated load. Test counterweight buffer at rated speed. Re-inspection required. 2/14/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency car lighting is not operational, likely indicating that the back-up power device has failed, fixture needs repaired. Re-inspection required 2/14/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two way communication is not working. Re-inspection required 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unable to perform the following tests: 125% lower & hold, set safeties full load full speed, car buffer full load full speed, counterweight buffer. Re-inspection required to complete inspection 6/16/2023