Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work. Will not activate 10/22/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work. Phone line dead to elevator controller 9/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.1.1 x Install self closing, self locking door on controller disconnect room. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.16.8 x Test standby power operation. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.18 - Traction drive machines 2.24 x Auxillary contacted on shunt and disconnect. 2.11 is not an Item Option and needs to be added. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x Control room illumination shall be 19 foot candles. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Hoistway shall be as near vertical as possible. Shall be capable of holding 150#/sq ft without deformation. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Seal all hoistway penetration to maintain fire rating. 8/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x NEC Secure conduit at top of hoistway. 8/10/2018