ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.18 - Traction drive machines
|
2.24
|
x
|
|
Auxillary contacted on shunt and disconnect. 2.11 is not an Item Option and needs to be added.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2 (Re-Inspection)
|
x
|
|
Control room illumination shall be 19 foot candles.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Hoistway shall be as near vertical as possible. Shall be capable of holding 150#/sq ft without deformation.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
x
|
|
Install self closing, self locking door on controller disconnect room.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
NEC Secure conduit at top of hoistway.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Seal all hoistway penetration to maintain fire rating.
|
8/10/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Telephone in car doesn't work. Phone line dead to elevator controller
|
9/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Telephone in car doesn't work. Will not activate
|
10/22/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.16.8
|
x
|
|
Test standby power operation.
|
8/10/2018
|