Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency bell & phone not working on emergency power. Re-inspection required 3/12/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light not working on emergency power. Re-inspection required 3/12/2025
MO Minimum : Elevators (H) - Machine Rooms (H)8 x Mainline disconnect auxillary contact for switch position monitoring shall be installed in the disconnect to prevent electrical shock.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Provide proper disconnect wiring to prevent auxillary battery operation when the disconnect is in the off position.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Auxiliary battery lowering device removed no variance applied for Replace.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Need to re-program phone, not working. Re-inspection required 6/7/2022