ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
update the Firefighters' service test log
|
2/23/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
|
|
does not have Maintenance Control Program (MCP) documents in the machine room
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone line was dead, provide working phone line 2.27.1.1.1
|
7/31/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency phone is calling a number that goes straight to a busy signal, program phone to a good number
|
8/1/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - n/a
|
na
|
x
|
|
siderail clear distance less than 4.5"
|
3/7/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
repair the fire service phase 1 keyswitch, it did not recall the elevator
|
6/19/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
two-way communication failed. repair the phone line
|
2/23/2021
|