Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Provide/Maintain/Enclose/Seal all seams/holes/penetrations and etc. in the hositway with fire-resistive construction/material (2-hr)
conversion conversion n/a Elevator released for temporary use until 2-23-2018. Correct / Address all deficiencies and schedule an inspection by 2-23-2018
conversion conversion n/a Provide updated/charged annually Class 'ABC' Fire Extinguisher
conversion conversion n/a The elevator machinery/control space (Top-of-Hoistway) shall be provided with an independent ventilation or air-conditioning
conversion conversion n/a Provide annual billing / contact info. Needing to obtain:
conversion conversion n/a The pit ladder shall have a clear distance of not less than 4.5 inches from the centerline of the rungs to the nearest permanent object in back of the pit ladder
conversion conversion n/a The pit ladder shall extend not less than 48 inches above the sill of the pit access door