A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Existing phone not working. Repair as needed
|
1/20/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work, Re-inspection required
|
9/30/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Perform the following tests to complete the Cat 5 full load test. Pull out and pull through force of govenor. Tripping speed of governor switch and governor jaws. Unintended movement. car safeties at rated speed with rated load. Re-inspection required
|
11/14/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
elevator control room door to be self locking.
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
elevator control room to be self closing.
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room doors need to be self closing and self locking
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(b)
|
|
|
Machine space doors to be self closing
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(b)
|
|
|
Machine room door to be self locking
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Closet next to elevator is an elevator room, remove all non elevator related equipment from this space.
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Elevator room doors are to be self closing and self locking
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(k)
|
|
|
Provide feeder location on main line disconnect
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
|
|
Provide feeder location on main line disconnect.
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
|
|
Provide feeder location on 110v. disconnect.
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
|
|
Provide feeder location on main line disconnect
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
|
|
Provide feeder location on 110 v disconnect
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide MCP
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide MCP
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
provide an on-site maintenance control program.
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide complete MCP
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
remove all non elevator equipment from contol space
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Closet next to elevator is in machine space, remove non elevator equipment
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(h)
|
|
|
Closet next to elevators is a machine space. Remove all non elevator related equipment
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher is expired in the main disconnect room on top floor. Have serviced or replaced
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
provide a current tested fire extinguisher in elevator control room.
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher expired. In the main disconnect room on top floor
|
10/30/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Expired fire extinguisher
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
Fire extinguisher is expired, have serviced or replaced. Re-inspection required
|
10/7/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current tested fire extinguisher in elevator machine room
|
12/7/2022
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Expired
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
provide feeder location on main line disconnect
|
12/7/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
provide feeder location on car light disconnect
|
12/7/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated Missouri operating certificate in machine room. Top floor electrical room
|
10/30/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
|