Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency/standby power operating of the elevator shall be tested. 4/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage 8.6.5.5.2 - Jack head drain tube to be routed to a measurable container in pit. Currently, one line drains directly to tank. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and related on-site documentation shall be provided in the machine room. Fire service testing shall be documented monthly. Missing entire MCP except fire service and oil loss log. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 There is no MCP on-site. 1/10/2024