Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and related on-site documentation shall be provided in the machine room. Note: Fire service testing shall be documented monthly. Missing entire MCP except fire service and oil loss log. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Car door restrictor shall work at all floors. 3/30/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Emergency/standby power operation of the elevator shall be tested. 4/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage No No Jack head drain tube to be routed to a measurable container in pit. Currently 1 line drains directly to tank. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No No MCP on-site. 1/10/2024