Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In cab emergency telephone shall work. 2/11/2019
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Missing braille/tactile plates on all entrances. 6/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The ETS system and NTS system shall be tested. 12/21/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. The extinguisher is expired. 3/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current tested fire extinguisher shall be provided in the elevator machine room. 1/28/2020
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Beveling required on hoistway ledges exceeding 4”. 6/24/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems x Replace the missing sight edge on hoistway door, B Floor, left side. 1/28/2020
A17.1-2016 : Elevators 3.2 - Car top light and outlet 2.14.7.1.4 Provide means to have 10fc of light anywhere on car top. 6/24/2024
A17.1-2016 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.10.2.3 Toe Board Missing toe board on car top 6/24/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit light shall be operational.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) x When the car is on phase two fire service and the call cancel button is activated, all registered calls shall be canceled and a traveling car shall stop at or before the next available landing. The CCB cancels the car calls as required, but the car continues to run until reaching the terminal floor. This will happen in both the up and down directions when running on phase two.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate. 1/28/2020