ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Obtain and display a current state operating certificate in the machine room
|
1/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Have the fire extinguisher re-certified as yours expired last year.
|
1/1/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide an MCP in the machine room
|
5/2/2022
|
A17.2-2014 : Elevators
|
2.3 - Lighting and receptacles
|
2.3.1
|
x
|
|
Install lighting in the machine space to provide a min of 20 ftc at the floor
|
4/24/2019
|
A17.2-2014 : Elevators
|
2.7 - Fire Extinguisher
|
2.7.1
|
x
|
|
Install a type ABC fire extinguisher in the machine space
|
4/24/2019
|
A17.2-2014 : Elevators
|
3.10 - Hoistway construction
|
3.10.1
|
x
|
|
Fire seal all the open penatrations into the hoistway.
|
4/24/2019
|
A17.2-2014 : Elevators
|
2.1 - Access to machine space
|
2.1.1(a)
|
x
|
|
Change out the door lock to the machine space it is to be always locked outside never locked inside.
|
4/24/2019
|