Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x phone kept trying to dial out but didn't have the "correct code" per the message, check that the phone is dialing a valid number 8/23/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication not working. phone line not active. 8/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in car not working. phone line dead 12/16/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Maintenance Control Program (MCP) documents are not on site 3/4/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.40 - Maintenance Records 2.26.1.5 Inspection Operation With Open Door Circuits. There is no Maintenance Record Documentation on site. 11/4/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.3.1.2(j) the fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually 3/4/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 2.12.7 Lower landing hoistway access operation failed. 11/4/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 2.12.7 Lower landing hoistway access, movement of the car shall be limited to travel as per 2.12.7.3.6. The car will not stop in the up direction. 11/4/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Fire fighters service test log has not been filled out since November 2020 3/4/2022