Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x The front of the disconnects in the machine space shall be flush with the controller to provide code required electrical clearance as specified in the NEC. 8/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.7.2.21 x 2.20.4 - Hoist ropes are 8mm and the minimum allowable size in 9.5mm. Customer to apply for a variance to allow undersized ropes. 8/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.7.2.21 2.20.4 - Hoist ropes are 8mm and the minimum allowable size in 9.5mm. Customer to apply for a variance to allow undersized ropes.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x A sump pump is required in the pit. 8/15/2019