Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.11.2.1.4(b) x 2.11.11.8 - Fire guides are missing from the hoistway door. 12/6/2022
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.7.2 Seizing of Rope Ends 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 2.21 2.21.1.2 - Counterweight hold down clamps need to be set properly. They are currently 3" above weight stack.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/18/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. (2nd Notice) 12/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 x Fire gibs are missing from some of the hoistway doors. 10/18/2023
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.9.5 Wedge Rope Sockets Hoist rope tail end retaining clips shall be properly spaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Inspection and testing incomplete. Remaining items: 125% 1 floor run down, 0% up unintended motion and 125% down unintended motion, 100% safety set, slide, EBR, governor pullout and pull-thru, elect/mech speeds. 8/23/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing MCP Fire Service testing must be properly documented monthly on log sheet.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces Non-elevator related items shall not be stored in machine room.
A17.2-2014 : Elevators 1.6 - Car emergency signal 1.6.1 x The emergency phone shall work with 24/7 support. 11/11/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 12/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/18/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Remove excess debris.