A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Install phone line for the emergency phone and program.
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
Install a shunt trip means to prmove the application of water in the machine room. If smoke detectors are use as a trip means for the shunt it shall be within 24 inchws of the sprinkler head.
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Seal all machine room penetrations
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
x
|
|
Machine space needs a rated ceiling to maintain the fire rating.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Close all hoistway penetrations
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Cover pit sump even with the pit floor
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
x
|
x
|
Install a smoke detector in the elevator machine room for fire recall.
|
|