Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Install phone line for the emergency phone and program.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x Cover pit sump even with the pit floor
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Close all hoistway penetrations
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Machine space needs a rated ceiling to maintain the fire rating.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation x x Install a smoke detector in the elevator machine room for fire recall.
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Seal all machine room penetrations
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x Install a shunt trip means to prmove the application of water in the machine room. If smoke detectors are use as a trip means for the shunt it shall be within 24 inchws of the sprinkler head.