A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit must be kept free of Oil. 8.6.4.7.4
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19.4.1
|
|
|
Electronic controlled valve required to be shut off manually
|
4/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.4
|
|
|
Electronci controled required to be shut off manually to be accessed only outside of the hoistway
|
4/27/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
|
|
Pressure Gage Fieeings-Only be accssed from outside of the hoistway
|
4/27/2020
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5 Gland Packing and Seals
|
x
|
|
Must repair/replace Jack packing due to excessive oil leakage. 8.6.5.5.1
|
11/9/2022
|