A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
a copy of the state operating certificate is to be posted in the disconnect room
|
2/1/2021
|
A17.2-2014 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
6.5.1
|
x
|
|
Could not perform Phase I and Phase II Fire Service.
|
1/11/2019
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
does not have maintenance control program on site documentation
|
2/1/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log is to be posted in the disconnect room
|
2/1/2021
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
|
|
Sump pump cover is to be secured to the pit floor so it will not move
|
2/2/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
the emergency lights did not work, the charging board is not working and needs to be replaced
|
1/18/2021
|