Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.22 - Wire rope fastening and hitch plate 2.20.5 x Counterweight end of hoist cables have 3 different springs. To maintain even cable tension all springs shall be the same. 10/7/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties Table 2.17.3 x x Repair car safeties to allow for required stopping distance. Stopping 6" code minimum is 10" 10/7/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.2.2 x Install cover plate on end of the machine beam at entrance of machine deck and paint or cover with caution tape. 10/7/2019
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not operating correctly. The location of the elevator cannot be identified by the monitoring service operator. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. 6/21/2021