                        A17.1-2016 : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        8.6.4.7 Cleaning of Pits
                     | 
                    
                     | 
                    
                     | 
                    
                        Remove the water and mold from the pit.
                     | 
                    
                        12/16/2021
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        5.1 - Pit access, lighting, stop switch, and condition
                     | 
                    
                        8.6.4.7 Cleaning of Pits
                     | 
                    
                     | 
                    
                     | 
                    
                        The pit shall be kept clean and free of oil and debris.
                     | 
                    
                        
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        8.6.5.16.5 Over Speed Valve Testing
                     | 
                    
                     | 
                    
                     | 
                    
                        This elevator is equipped with an overspeed valve. Based on the installation date of 2018, a category 5 test shall be performed on the overspeed valve in 2023. The valve shall be sealed and tagged after the category 5 test.
                     | 
                    
                        10/19/2022
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The in car emergency telephone shall be operational.
                     | 
                    
                        10/19/2022
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The in car emergency alarm bell shall be operational, with and without main power.
                     | 
                    
                        10/31/2023
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.17 - Standby power operation
                     | 
                    
                        3.26.10 (Auxiliary Power)(Re-Inspection)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Auxiliary power lowering operation is not functional.
                     | 
                    
                        
                     |