ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
8.11.2.1.1(d)
|
x
|
|
Elevator flooring has not been installed.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
MRL unit with Control @ 2nd level in landing door jamb. Control lighting shall be 19fc
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
x
|
|
Fire Extinguisher shall be accessible to Control area @ 2nd landing.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
In Elevators provided with Firefighters Emergency Service & Sprinkler system a sump pump shall be provided.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
Ref A17.1a Item 2.8.3.4 (a)(b) when sprinklers are installed in hoistway all electrical equipment below 48 inches shall be weatherproof NEMA 4.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
Ref A17.1a Section 2.8.3.2(b) Sprinkler located in MRL Control Lobby area shall be provided a heat detector to initiate elevator power shutdown.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19.4.1
|
x
|
|
MRL TKE Endura manually shut off valve shall be provided between the hydraulic machine & hydraulic jack outside the hoistway.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.4
|
x
|
|
The Manually Lowering Valve. Where the hydraulic machine is located in the hoistway, the manual lowering valve shall only be accessible to elevator personnel from outside the hoistway.
|
3/11/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.5
|
x
|
|
MRL Endura Pressure Gauge Fittings. Where the hydraulic machine is located in the hoistway, the pressure gauge fittings shall be accessible to the elevator personnel from outside the hoistway.
|
3/11/2022
|