Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x In Elevators provided with Firefighters Emergency Service & Sprinkler system a sump pump shall be provided. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x Ref A17.1a Item 2.8.3.4 (a)(b) when sprinklers are installed in hoistway all electrical equipment below 48 inches shall be weatherproof NEMA 4. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 x MRL TKE Endura manually shut off valve shall be provided between the hydraulic machine & hydraulic jack outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 x The Manually Lowering Valve. Where the hydraulic machine is located in the hoistway, the manual lowering valve shall only be accessible to elevator personnel from outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 x MRL Endura Pressure Gauge Fittings. Where the hydraulic machine is located in the hoistway, the pressure gauge fittings shall be accessible to the elevator personnel from outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) x Elevator flooring has not been installed. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x MRL unit with Control @ 2nd level in landing door jamb. Control lighting shall be 19fc 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) x Fire Extinguisher shall be accessible to Control area @ 2nd landing. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x Ref A17.1a Section 2.8.3.2(b) Sprinkler located in MRL Control Lobby area shall be provided a heat detector to initiate elevator power shutdown. 3/11/2022