ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided Yes No In Elevators provided with Firefighters Emergency Service & Sprinkler system a sump pump shall be provided. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No Ref A17.1a Item 2.8.3.4 (a)(b) when sprinklers are installed in hoistway all electrical equipment below 48 inches shall be weatherproof NEMA 4. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19.4.1 Yes No MRL TKE Endura manually shut off valve shall be provided between the hydraulic machine & hydraulic jack outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.4 Yes No The Manually Lowering Valve. Where the hydraulic machine is located in the hoistway, the manual lowering valve shall only be accessible to elevator personnel from outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.5 Yes No MRL Endura Pressure Gauge Fittings. Where the hydraulic machine is located in the hoistway, the pressure gauge fittings shall be accessible to the elevator personnel from outside the hoistway. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) Yes No Elevator flooring has not been installed. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) Yes No MRL unit with Control @ 2nd level in landing door jamb. Control lighting shall be 19fc 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Yes No Fire Extinguisher shall be accessible to Control area @ 2nd landing. 3/11/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) Yes No Ref A17.1a Section 2.8.3.2(b) Sprinkler located in MRL Control Lobby area shall be provided a heat detector to initiate elevator power shutdown. 3/11/2022