ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
2.41 : MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
11/24/2020
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.11.3.1.2(aa)
|
|
|
Provide a code data plate conforming to sec 8.9
|
12/6/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
2.8.1
|
|
|
Provide cover for wiring in a j-box in the machine room with wiring sticking out of box
|
8/28/2024
|
A17.1-2016 : Elevators
|
2.34 - Flexible Hydraulic Hose and Fitting Assemblies
|
8.6.5.6
|
|
|
Provide replacement date for the hose in a permanent marking on the hydraulic hose
|
8/28/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
3.19.4.7.1 Overspeed Valve Test
|
x
|
|
OSV test could not be performed at this time. Re-inspection required
|
8/28/2024
|