Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 2.8.1 Provide cover for wiring in a j-box in the machine room with wiring sticking out of box 8/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 3.19.4.7.1 Overspeed Valve Test x OSV test could not be performed at this time. Re-inspection required 8/28/2024
A17.1-2016 : Elevators 2.14 - Code data plate 8.11.3.1.2(aa) Provide a code data plate conforming to sec 8.9 12/6/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 2.41 : MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. 11/24/2020
A17.1-2016 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 8.6.5.6 Provide replacement date for the hose in a permanent marking on the hydraulic hose 8/28/2024