Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)6 x x Landing gate interlock is broken.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Hold function is not working.
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.11.2.1.2(gg) x x not able to test empty car safeties no cord on site to do test with 4/5/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(b) The written MCP needs to specify the maintenance tasks, and tests, and shall list the associated requirement of section 8.6 8/5/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Written maintenance records shall list the requirement of section 8.6 that pertains to the task, and tests, with specified scheduled intervals. 8/5/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records no mcp on site 8/5/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current cirt displayed 8/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 8/5/2025