Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/18/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 12/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with current test tag shall be mounted convenient to the top landing entrance. Note: This unit is an MRL with the elevator control and means to test in the top landing entrance. 12/18/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on site. 12/18/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Hoistway door bottom retainers required 10/17/2020