MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)4
|
|
|
Accordion doors have split hinges allowing items to pass through during operation without interrupting operation, or opening the gate switch.
|
3/17/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
All 3 landing doors our outside of the 3/5 rule with regard to swing type landing doors.
|
3/17/2020
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)2
|
|
|
Car frame bent out of place.
|
3/17/2020
|
MO Minimum : Elevators
|
(N) - Guide Rails
|
(N)1
|
|
|
Car stabilizer rail bracket loose on cartop.
|
3/17/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)2
|
|
|
Cartop has water damage that lessens the capability to sustain the required 300 pound minimum load.
|
3/17/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and bell not working
|
3/4/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Hoistway door to sill clearance over 3/4 in.
|
4/18/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Hoistway door to sill clearance over 3/4 inch.
|
3/12/2025
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Main hoisting cables badly rouged and worn. Replace.
|
3/17/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
Provide pit switch in pit.
|
3/17/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Wiring in hoistway must be in approved conduit.
|
3/17/2020
|