Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary power lowering is not working. Re-inspection required 7/10/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Battery lowering device is not working, needs repaired. Re-inspection required
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The lighting in the elevator machine room is not sufficient, the lighting shall not be less than 10 foot candles at the floor level
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State certificate in machine room 10/13/2020
MO Minimum : Elevators (I) - Pits (I)8 Provide sump hole cover 10/13/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide a proper code data plate for mod 12/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide lighting of the 19fc at floor in all machine room areas 12/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) Provide sump hole cover 8/4/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room 8/4/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room